Product introduction

Product Overview

ItemDescription
Product NameFrequency Inverter/ AC Drive
Model NumberV5-H-6TxxxG, V5−H−BTxxxG
Power Range15kW-710kW
Rated Input Voltage3 phase 380V/480V
Rated Output Voltage3 phase 0 to rated input voltage
Input Frequency50Hz/60Hz
Applicable MotorAsynchronous Motor
Control ModeV/F Control, Vector Control, Sensor-less Vector Control, Vector Torque Control
CommunicationModbus 485 RTU
IP ClassStandard IP20
Overload Capacity150% 1 minute, 180% 10 seconds, 200% 0.5 second, interval: 10 minutes (inverse time lag feature)

 

Medium Voltage Drives Feature

V&T Vector Torque Drive Higher saving-energy effect and Less reactive current

■ Outdoor digital control cabinet, thermostatic control cabinet suit ,high and low temperature ambient for long-term reliable work

■ Excellent control performance for open-loop vector control, accurate speed identification and rotor flux orientation, and torque can respond quickly and operate stably at 0.25hz load change

■ Excellent current and voltage control technology, repeatedly and alternately accelerated and decelerated with 0.1s instruction, and inverter operates stably ;

■ Wide voltage ;range, low voltage ;under fluctuated power, continuous working, strong adaptability

■ Convenient and continuous to adjust speed, perfect torque compensation function, normal to start motor with powerful power.

■ Mature power balance scheme can effectively solve power distribution in multi-point transmission.

■ The overload capacity can be optimized under low frequency.

■ Rich monitoring function, operation data can be recorded and saved by storage medium or wireless transmission.

Model Explanation

 

Product Catalogue

V5−H−6T□□□G ; 3 Phase 690V Constant Torque/Heavy-duty Applications

Power(kW)1518.522303745557590110132160185200220
Motor(kW)1518.522303745557590110132160185200220
OutputVoltage(V)3 phase 0Rated Voltage
Rated Current(A)202528354552658698120150176204220245
Overload capacity150% 1min180% 10 second 200% 0.5 secondinterval: 10 minutes (inverse time lag ;feature)
InputVoltage/ frequency3 phase 690V~790V;50Hz/60Hz
Allowable voltage range587V~793V;Voltage imbalance:≤3% ;allowable frequency fluctuation:±5%
Rated Current(A)253035404752658596116145168196210230
*Braking unitBuilt-in as standardExternal braking unit needed
IPIP20
Cooling modeForced air cooling
Power(kW)250280315355400450500560630
 

 

 

 

 

 
Motor(kW)250280315355400450500560630
 

 

 

 

 

 
OutputVoltage(V)3 phase 0Rated Voltage
Rated Current(A)275325350395435490545600680
 

 

 

 

 

 
Overload capacity150% 1min180% 10 second 200% ;0.5 secondinterval: 10 minutes (inverse time lag ;feature)
InputVoltage/ frequency3 phase 690V790V50Hz/60Hz
Allowable voltage range587V~793V;Voltage imbalance:≤3% ;allowable frequency fluctuation:±5%
Rated Current(A)255290335378415466520580655
 

 

 

 

 

 
*Braking unitExternal braking unit needed
IPIP20
Cooling modeForced air cooling

V5−H−BT□□□G ; 3 Phase 1140V Constant Torque/Heavy-duty Applications

Power(kW)

37

45

55

75

90

110

132

160

185

200

220

250

280

315

355

Motor(kW)

37

45

55

75

90

110

132

160

185

200

220

250

280

315

355

Output

Voltage(V)

3 phase 0~Rated Voltage

Rated Current(A)

25

31

38

52

58

73

86

104

115

132

144

162

180

208

225

Overload capacity

150% 1 min,180% 10 second, 200% 0.5 second,interval: 10 minutes (inverse time lag ;feature)

Input

Voltage/ frequency

3 phase 1140V;50Hz/60Hz

Allowable voltage range

960V~1300V;Voltage imbalance:≤3% ;allowable frequency fluctuation:±5%

Rated Current(A)

27

32

38

51

57

72

85

102

113

126

141

158

180

200

215

IP

IP20

Cooling mode

Forced air cooling

Power(kW)

400

450

500

560

630

710

         

Motor(kW)

400

450

500

560

630

710

         

Output

Voltage(V)

3 phase 0~Rated Voltage

Rated Current(A)

260

300

325

365

400

450

         

Overload capacity

150% 1 min,180% 10 second, 200% 0.5 second,interval: 10 minutes (inverse time lag ;feature)

Input

Voltage/ frequency

3 phase 1140V;50Hz/60Hz

Allowable voltage range

970V~1300V;Voltage imbalance:≤3% ;allowable frequency fluctuation:±5%

Rated Current(A)

260

300

325

365

400

450

         

IP

IP20

Cooling mode

Forced air cooling

 

Technical Specification

Control characteristics

Control mode

Vector Control

Starting torque

0.50Hz ;180%

Speed regulation range

1:100

Steady speed precision

± ;0.5%

Product functions

Key function

Under-voltage regulation, switchover of run command source(operation panel, terminal and communication), speed tracing function, multi− step frequency reference(up to 23 step frequency),S curve acceleration and deceleration, slip compensation, PID regulation, droop control, current limit, manual torque boost and auto torque boost,Multiple function input/output terminal.

Frequency setting method

operation panel setting、terminal UP/DN、upper computer communication、analog AI1, analog AI2,analog AI3、pulse DI, etc.

Frequency range

0.00~300.00Hz

Starting frequency

0.00~60.00Hz

Acceleration time and deceleration time

0.1~36000s

Dynamic braking

Braking unit action voltage:

AC690V: 800~1200V AC1140V:1700~2200V

DC braking

DC braking start frequency:0.00~300.00Hz;

DC braking current:0.0~120.0%;

DC braking time:0.0~30.0s;DC braking function does not required waiting time to start ;to realize quick braking

Magnetic flux braking

Enabled or disabled during deceleration are optional, the default setting is enabled

Unique functions

Multi-function M key

The unique multi-function key can be set to frequently used operations: such as JOG, emergency stop, switchover of run command source, switchover of parameters display mode, etc.

Multiple parameter display modes

Basic parameters display mode, fast parameters display mode, non−factory setting parameters display mode.

Parameters copy

The standard operation panel can realize the parameters upload, download and display the copy progress. Users can set to forbid overwriting the uploaded parameters

Function code hiding

Customers can customize the display and hide of any function code group

Dual 485 communication ports

Dual 485 communication ports support Modbus protocol (RTU). The maximum distance is 500 meters

Operation panel

Key type operation panel, Protection level: IP20 as standard, IP54 as option

Common DC bus

All series product support common DC bus

Independent duct

All series product adopts independent duct design and supports the installation of heat-sink outside the cabinet

Power-On-Self-Test

(POST)

Realizing the POST of internal and peripheral circuits, including motor grounded, abnormal +10V power supply output, analog input and disconnection, etc.

Protection function

Power supply under-voltage, over-current protection, over-voltage protection, interference protection, abnormal comparison level, motor data identification ;failure, module(IPM) protection, heat-sink over temperature protection, inverter overload protection, motor overload protection, peripheral protection, abnormal current detection, output short circuit to ground, interruption of power supply when in running status, abnormal input power, output phase loss, abnormal EEPROM protection, abnormal pre-charging contactor detection, temperature sampling disconnection, abnormal +10V power supply, abnormal analog input, motor over temperature protection(PTC), abnormal communication, abnormal software version compatibility, abnormal copying, terminal mutual exclusion detection, hardware overload protection

Environment

Operating site

The product should be mounted vertically in the electric control cabinet with good ventilation. Horizontal or other installation modes are not allowed. The cooling medium is the air. The product should be installed in the environment without dust, corrosive gas, combustible gas, oil mist, steam, drip and free from direct sunlight.Please install it in a place where it cannot be severe vibration and shock, and the maximum amplitude does not exceed 5.8m/S2 (0.6g)

Ambient temperature

−10 to +40ºC, the product must be de-rated rated output current for the ambient temperature between 40ºC to 50ºC, the rated output current must be de-rated for 1% per 1ºC temperature rise

Humidity

5 to 95%, no condensing

Altitude

0 to 2000m, the product must be de-rated rated output current for the altitude above 1000 meters, the rated output current must be de-rated for 1% per 100 meters rise

Vibration

3.5mm, 2~9Hz;10 m/s2,9~200Hz;15 m/s2,200~500Hz

Storage temperature

−40~+70℃

Function of Control Circuit Terminal

 

Installation Dimension

690V Voltage Class


 

 

V5−H−6T90G And below power class


 

 

 

V5−H−6T110G And above power class(accompany with pedestal )


 

 

V5−H−6T110G And above power class(no pedestal)

V5−H−6T Series Product Appearance,Installation Dimensions, Approximate Weight

Voltage

power(kW)

pedestal

Appearance size(mm)

Installation Dimensions(mm)

Weight(kg)

W

H

D

W1

H1

D1

T1

Hole d

690V

15~30

No

285

440

220

200

425

107.5

2.5

7

17

37~55

No

315

575

227

220

553

123.5

2.5

10

25

75~90

No

400

615

265

270

590

123.5

3.0

10

35

110~132

yes

465

1042

325

382

339

238

14

No

465

745

325

343

715

156

3.0

12

55

160~220

yes

540

1206

385

459

365

300

14

No

540

890

385

370

855

205.5

4.0

14

85

250~355

yes

700

1380

385

614

412

294

15

No

700

1010

385

520

977

210

4.0

14

125

400~630

yes

810

1698

425

728

418

339

15

No

810

1358

425

520

1300

210

4.0

14

215

Note: For 690V series inverters, air-cooled inverters are standard products, and explosion-proof inverters need to be customized according to customer needs. The installation dimensions of explosion-proof inverters can be flexibly changed according to customer requirements. If you have special needs, please contact our company R & D department. The company only provides explosion-proof inverter inner cores, and does not design and produce explosion-proof enclosures.

1140V Voltage Class


 

 

 

 
V5−H−BT37G~V5−H−BT250G power class ;                                                                                                       V5−H−BT280G~V5−H−BT710G power class

 

V5−H−BT Appearance, Installation Size and Approximate Weight

Voltage

Power(kW)

Appearance, Installation Size(mm)

Weight

(kg)

W

H

D

W1

H1

D1

d

1140V

37~132

590

1280

365

506

1255

271

14

80

160~250

800

1700

450

716

1669

351

14

130

280~500

1000

2552

800

880

2200

700

20

220

560~710

1200

2552

800

1080

2200

700

20

250

Notes:

♦ For the 1140V series inverter, the air-cooled inverter is a standard product, and the explosion-proof inverter needs to be manufactured at client’s requirements. Explosion-proof inverter’s installation size, can be customized at client’s requirements. If you have any special requirements, please contact research and development department in company.

♦ Company only provide explosion-proof inverter and inner core, not produce explosion-proof enclosure.

Applications


 

 

 

 

 

 

 

 

 

 

Industrial Control Inverters Representative Industry

An ac drive is a device that is used to control the speed of an electric motor. The use of VFDs, also known as variable speed drives (VSD), is becoming common in operating motors used in heating, ventilating, and air conditioning (HVAC) systems within buildings. As an advanced Inverter Drive Manufacturer, The Middle Voltage High-performance Universal Inverter of Shenzhen V&T Technologies Co.,Ltd. are widely used in Fan, Pump, Oilfield,Inner Parts for Safety and Explosion-proof Machine ,Mining Winch,Coal Mine,Hoist,Municipal Engineering, Rubber and Plastics Machine.

Download

undefined

undefined

Middle Voltage 690V 1140V High-performance Universal Inverter

Product Model:

V5-H-6T and V5-H-BT medium voltage series are high-performance vector control inverter. The product adopts the open-loop vector control technology with the current international advanced technology, which has the same excellent control performance with the international high-end drive. It further strengthened the reliability and environmental adaptability of the product, as well as the customized and professional design. This greatly meet the needs of various transmission applications.

Keywords:

Download File:


E-mail

Online Message

Ready to grow your business? Your next great business opportunity starts with an inquiry.